User Manual of EM760 High-Performance Inverter F00.04=0: digital frequency setting F00.07 The main frequency source A depends on the digital frequency setting F00.07. F00.04=1: AI1 F00.04=2: AI2 F00.04=3: AI3 F00.04=4: AI4 (extension card) The main frequency source A depends on the AI (percentage) * F00.16. The percentage corresponding to the input physical quantity of the AI terminal is set by the function codes F02.32 to F02.56. 100.00% is the percentage to the set value ofF00.16 (maximum frequency). F00.04=5: High-frequency pulse input (X7) The main frequency source A depends on the HDI (percentage) * F00.16.
The terminal X7 can also be used for high-frequency pulse input (set the terminal function F02.06 to “40: pulse input”), with the frequency range of 0.00-100.00kHz. The corresponding percentage of terminal input pulse frequency is set by F02.26-F02.29. 100.0% is the percentage relative to the set value ofF00.16 (maximum frequency). F00.04=6:
Percentage setting of main frequency communication ● Ifthe master-slave communication (F10.05=1) is enabled and the inverter works as the slave (F10.06=0), the main frequency source A is set to “700FH (master-slave communication setting) * F00.16 (maximum frequency) * F10.08 (slave receiving proportional coefficient)”, and the 700FH data range is -100.00% to 100.00%. ● For general communication (F10.05=0): The main frequency source A is set to “7001H (communication percentage setting of the main channel frequency A) * F00.16 (maximum frequency)”; data range of 7001H: - 100.00%~100.00%. F00.04=7:
Direct setting of main frequency communication The main frequency source A is set to “7015H (communication setting of the main channel frequency A)”; data range of 7015H: 0.00~F00.16 (maximum frequency). 79 Function code Function codename Parameter description Unit Default setting Attribute F00.04 Options of main frequency source A 0: digital frequency setting F00.07 1: AI1 2: AI2 3: AI3 4: AI4 (expansion card) 5: high frequency pulse input (X7) 6: Percentage setting of main frequency communication 7: Direct setting of main frequency communication 0 〇