omron — Multi-function Input Selection

4-2 Function Mode RDY (Ready) Function This function prepares for Inverter output to rotate the motor immediately after a RUN command is input. •When this function is enabled, the RUN (during RUN) LED indicator is always lit, since the Inverter is in output status even though the motor stops. •Allocate '52 (operation ready)' to any of multi-function inputs C001 to C006, or set b151 to '01'. Refer to the table below for the correlation when the multi-function input '52' and b151 are set simultaneously. •When this function is enabled, data other than the parameters changeable during operation cannot be changed.

4 Functions The 3G3MX has six multi-function inputs [S1], [S2], [S3], [S4], [S5] and [S6]; two open collector out- put terminals [P1], [P2]; two relay output terminals [MA] and [MB] (SPDT contact); and one analog output terminal [AM]. Multi-function Input Selection • You can allocate the following functions to any of multi-function inputs S1 to S6 (C001 to C006, C201 to C206) to operate the set function. •You can select NO- or NC-contact input for each multi-function input S1 to S6. 4-40 Parameter No. Function name Data Default setting Unit b151 Ready function selection 00: Disabled 01: Enabled 00  Multi-function input terminal "52" OFF ON b151 setting 00 OFF ON 01 ON ON