4-2 Function Mode •The same two functions cannot be allocated to the multi-function inputs. If you attempt to allocate the same two functions to the terminals by mistake, the terminal where you allocated the function last takes precedence. The previous data is set to "255", and the terminal function is disabled. 4 Functions * To switch to the 2nd control, allocate 08 (SET) to the multi-function input and then turn it on. •Function codes C001/C201 to C006/C206 correspond to multi-function inputs S1 to S6 respectively. •'19: Thermistor input' can be allocated only to multi-function input S6. 4-41 Parameter No. Function name Data Default setting Unit C001 Multi-function input 1 selection 00:
FW(forward) 01: RV(reverse) 02: CF1 (multi-step speed binary 1) 03: CF2 (multi-step speed binary 2) 04: CF3 (multi-step speed binary 3) 05: CF4 (multi-step speed binary 4) 06: JG (jogging) 07: DB (external DC injection braking) 08: SET (2nd control) 09: 2CH (2-step acceleration/deceleration) 11: FRS (free run) 12: EXT (external trip) 13: USP (USP function) 15: SFT (soft lock) 16: AT (analog input switching) 18: RS (reset) 19: PTC (thermistor input) 20: STA (3-wire start) 21: STP (3-wire stop) 22: F/R (3-wire forward/reverse) 23: PID (PID enabled/disabled) 24: PIDC (PID integral reset) 27: UP (UP/DWN function accelerated) 28: DWN (UP/DWN function decelerated) 29:
UDC (UP/DWN function data clear) 31: OPE (forced operator) 50: ADD (frequency addition) 51: F-TM (forced terminal block) 52: RDY (ready function) 53: SP-SET (special 2nd function) 255:
No function 00 C201 *2nd multi-function input 1 selection C002 Multi-function input 2 selection 01 C202 *2nd multi-function input 2 selection C003 Multi-function input 3 selection 18 C203 *2nd multi-function input 3 selection C004 Multi-function input 4 selection 12 C204 *2nd multi-function input 4 selection C005 Multi-function input 5 selection 02 C205 *2nd multi-function input 5 selection C006 Multi-function input 6 selection 03 C206 *2nd multi-function input 6 selection C011 Multi-function input 1 operation selection 00: NO 01: NC • NO contact: "ON" with the contact closed, "OFF" with the contact open. • NC contact: "ON" with the contact open. "OFF" with the contact closed.
• For the RS terminal, only NO contact is available. 00 C012 Multi-function input 2 operation selection 00 C013 Multi-function input 3 operation selection 00 C014 Multi-function input 4 operation selection 00 C015 Multi-function input 5 operation selection 00 C016 Multi-function input 6 operation selection 00