4-2 Function Mode 4 Functions •There's no indication of 2nd control functions on the display. You'll see which one is enabled by checking whether the terminal is turned on/off. •Switch the SET terminal during stop or free run status, not during operation. External Trip Use this function to trip the Inverter according to the peripheral system conditions. •When the EXT terminal is turned on, E12 is displayed and the Inverter trips to stop output. •Allocate 12 (EXT) to the desired multi-function input. RUN commands FW and RV EXT terminal Motor rotation speed RS terminal Alarm output terminal 4-46 Parameter No.

Function name Selection SET SP-SET b022/b222 Overload limit level No Yes b023/b223 Overload limit parameter No Yes b028/b228 Overload limit source selection No Yes C001/C201 Multi-function input 1 selection No Yes C002/C202 Multi-function input 2 selection No Yes C003/C203 Multi-function input 3 selection No Yes C004/C204 Multi-function input 4 selection No Yes C005/C205 Multi-function input 5 selection No Yes C006/C206 Multi-function input 6 selection No Yes C041/C241 Overload warning level No Yes H003/H203 Motor capacity selection No Yes H004/H204 Motor pole number selection No Yes H006/H206 Stabilization parameter No Yes H007/H207 Motor voltage selection No Yes Data Symbol Function name Status Description 12 EXT External trip ON Sets the motor to free-run status by shutting off output.