omron — Communication Function

4-2 Function Mode 4 Functions *1. The Inverter's rated current is "1000". *2. The second decimal place is ignored when the value is over 10000 (100.0 seconds). 4-86 Register No. Function name Parameter No. R/W function Data Resolution 00B7h AM selection C028 R/W 0: F (Output frequency) 1: A (Output current)  00B8h Multi-function output terminal P1 contact selection C031 R/W 0: NO 1: NC  00B9h Multi-function output terminal P2 contact selection C032 R/W 0: NO 1: NC  00BAh Relay output (MA, MB) contact selection C036 R/W 0: NO 1:

NC  00BBh Overload warning level C041 R/W 0 to 20000 *1 0.01 [%] 00BCh Arrival frequency during acceleration C042 R/W 0 to 4000 0.1 [Hz] 00BDh Arrival frequency during deceleration C043 R/W 0 to 4000 0.1 [Hz] 00BEh PID deviation excessive level C044 R/W 0 to 1000 0.1 [%] 00C0h Not used    00C1h Not used    00C2h Not used    00C3h Not used    00C4h Not used    00C5h Not used    00C6h Not used    00C7h FV adjustment C081 R/W 0 to 2000 0.1 [%] 00C8h FI adjustment C082 R/W 0 to 2000 0.1 [%] 00C9h AM offset adjustment C086 R/W 0 to 100 0.1 [V] 00CAh Not used    00CBh Not used    00CCh Not used    00CDh Not used    00CEh Not used    00CFh UP/DWN selection C101 R/W 0:

Does not store the frequency data 1: Stores the frequency data  000Dh Reset selection C102 R/W 0: Trip reset at power-on 1: Trip reset at power-off 2: Enabled only during trip (Reset at power-on)  00D1h Not used    00D2h Not used   