7-1 Standard Specification List „ Single/3-phase 200-V Class 7 „ Common Specifications Specifications 7-2 Item 1/3-phase 200-V class Model name (3G3MX-) AE002 AE004 AE007 AE015 AE022 Applicable motor capacity *1 kW 0.2 0.4 0.75 1.5 2.2 HP 1/4 1/2 1 2 3 Rated output capacity (kVA) 200 V 0.5 0.8 1.3 2.7 3.8 240 V 0.6 1.2 2.0 3.3 4.5 Rated input voltage 1/3-phase 200-10% to 240+10% 50/60 Hz ±5% Rated output voltage *2 3-phase 200 to 240 V (Cannot output voltage higher than incoming voltage.) Rated output current (A) 1.6 2.6 4.0 8.0 11.0 Weight (kg) 0.7 0.85 0.9 1.8 1.8 Cooling method Self-cooling Forced-air-cooling Braking torque At short-time deceleration *3 At capacitor feedback Approx.
50% Approx. 20% to 40% For mounting discharge resistance Approx. 150% Approx. 100% Approx. 80% Minimum connection resistance (Ω) 100 100 50 50 35 Item Specifications Enclosure rating *4 Semi-closed (IP20) Control Control Method Phase-to-phase sinusoidal modulation PWM Output frequency range *5 0.5 to 400 Hz Frequency precision *6 Digital command: ±0.01% of the max. frequency Analog command: ±0.2% of the max. frequency (25°C ± 10°C) Frequency setting resolution Digital setting: 0.1 Hz Analog setting: Max.
frequency/1000 Voltage/Frequency characteristics V/f characteristics (constant/reduced torque) Overload current rating 150% for 1 min Acceleration/Deceleration time 0.01 to 3000 s (line, S-shape curve), 2nd acceleration/deceleration setting available Starting torque 200% min./1 Hz Carrier frequency modification range 2.0 to 14.0 kHz DC injection braking Starts at a frequency lower than that in deceleration via the STOP command, or via an external input.
(Level and time settable.) Protective Functions Overcurrent, overvoltage, undervoltage, electronic thermal, temperature error, ground-fault overcurrent at power-on status, overload limit, incoming overvoltage, external trip, memory error, CPU error, USP error, internal communication error, BRD error, overvoltage protection during deceleration, overcurrent suppression