3-7 Parameter List Extended Function Mode 3 Operation * 2nd control is displayed when '08 (2nd control)' is allocated to one of multi-function inputs from C001 to C006. 3-21 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Page Basic setting A001 Frequency reference selection 00: Digital Operator (FREQ adjuster) 01: Terminal 02: Digital Operator (F001) 03: Modbus communication 10: Frequency operation result 00 No 4-7 4-66 A201 *2nd frequency reference selection 00 No 4-7 A002 RUN command selection 01: Terminal 02: Digital Operator 03:
Modbus communication 02 No 4-8 4-66 A202 *2nd RUN command selection 02 No 4-8 A003 Base frequency 30. to Max. frequency [A004] 60. No Hz 4-8 A203 *2nd base frequency 30 to Max. frequency [A204] 60. A004 Maximum frequency 30. to 400. 60. No Hz 4-9 A204 *2nd maximum frequency 60. Analog input A005 FV/FI selection 00: Switches between FV/FI via terminal AT 01: Disabled (Outputs FV+FI) 02: Switches between FV/VR via terminal AT 03: Switches between FI/VR via terminal AT 00 No 4-10 A011 FV start frequency 0.0 to Max. frequency 0.0 No Hz 4-10 A012 FV end frequency 0.0 to Max. frequency 0.0 No Hz 4-10 A013 FV start ratio 0. to 100. 0. No % 4-10 A014 FV end ratio 0. to 100. 100.
No % 4-10 A015 FV start selection 00: External start frequency (A011 set value) 01: 0 Hz 01 No 4-10 A016 FV, FI sampling 1. to 17. 8. No 4-11