omron — Extended Function Mode

3-7 Parameter List 3 Operation * 2nd control is displayed when '08 (2nd control)' is allocated to one of multi-function inputs from C001 to C006. 3-22 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Page Multi-step speed, Jogging A020 Multi-step speed reference 0 0.0/Starting frequency to Max. frequency 6.0 Yes Hz 4-5 4-42 A220 *2nd multi-step speed reference 0 0.0/Starting frequency to 2nd max. frequency 6.0 Yes Hz A021 Multi-step speed reference 1 0.0/Starting frequency to Max.

frequency 0.0 Yes Hz 4-42 A022 Multi-step speed reference 2 0.0 A023 Multi-step speed reference 3 0.0 A024 Multi-step speed reference 4 0.0 A025 Multi-step speed reference 5 0.0 A026 Multi-step speed reference 6 0.0 A027 Multi-step speed reference 7 0.0 A028 Multi-step speed reference 8 0.0 A029 Multi-step speed reference 9 0.0 A030 Multi-step speed reference 10 0.0 A031 Multi-step speed reference 11 0.0 A032 Multi-step speed reference 12 0.0 A033 Multi-step speed reference 13 0.0 A034 Multi-step speed reference 14 0.0 A035 Multi-step speed reference 15 0.0 A038 Jogging frequency 0.00/Starting frequency to 9.99 6.00 Yes Hz 4-43 A039 Jogging stop selection 00: Free-run stop 01:

Deceleration stop 02: DC injection braking stop 00 No  4-43