4-1 Monitor Mode Output Voltage Monitor [d013] Displays the output voltage value (Vac) of the Inverter. The monitor LED indicator "V" lights up. (Display) 0. to 600.: Displays in increments of 1 V. Total RUN Time [d016] Displays the Inverter RUN time. 4 (Display) 0. to 9999. : Displays in increments of 1 hour. 1000 to 9999 : Displays in increments of 10 hours. 100 to 999 : Displays in increments of 1000 hours. Functions Power ON Time Monitor [d017] Displays the total power ON time of the Inverter. (Display) 0. to 9999. : Displays in increments of 1 hour. 1000 to 999 : Displays in increments of 10 hours. 100 to 999 : Displays in increments of 1000 hours.
Fault Frequency Monitor [d080] •Displays the number of times the Inverter has tripped. (Display) 0. to 9999. : Displays in increments of 1 time. 1000 to 6553 : Displays in increments of 10 times. Fault Monitors 1 [d081], 2 [d082], 3 [d083] •Displays the details of the last three trips. The most recent trip is displayed on trip monitor 1. (Display) •Factor (E01 to E35) *1 •Output frequency at the time of tripping (Hz) •Output current at the time of tripping (A) •Internal DC voltage at the time of tripping (V) •Total RUN time before the trip (hr) •Total power supply time before the trip (hr) *1. Refer to "Error Code List" (page 5-1) or "Trip Monitor Display" (page 5-4). 4-3