omron — Modbus-RTU Method

4-4 Communication Function 4 Functions 4-195 Register No. Function name Function code R/W Monitor and setting parameters Resolution 1440h Not used    1441h Thermal warning level C061 R/W 0 to 100 1 [%] 1442h Alarm code selection C062 R/W 0: Disabled 1: 3 bits 2: 4 bits  1443h 0-Hz detection level C063 R/W 0 to 10000 0.01 [Hz] 1444h Fin overheat warning level C064 R/W 0 to 200 1 [°C] 1445h to 144Ah Not used    144Bh Communication speed selection (Baud rate selection) C071 R/W 2: Loop-back test 3: 2400 bps 4: 4800 bps 5: 9600 bps 6: 19200 bps  144Ch Communication station No. selection C072 R/W 1 to 32  144Dh Communication bit length selection C073 R/W 7: 7 bits 8:

8 bits  144Eh Communication parity selection C074 R/W 0: No parity 1: Even 2: Odd  144Fh Communication stop bit selection C075 R/W 1: 1 bit 2: 2 bits  1450h Communication error selection C076 R/W 0: Trip 1: Trip after deceleration stop 2: Ignore 3: Free-run stop 4: Deceleration stop  1451h Communication error timeout C077 R/W 0 to 9999 0.01 [s] 1452h Communication wait time C078 R/W 0 to 1000 1 [ms] 1453h Communication method selection C079 R/W 0: ASCII 1:

Modbus-RTU  1454h Not used    1455h FV adjustment C081 R/W 0 to 65530 1 1456h FI adjustment C082 R/W 0 to 65530 1 1457h FE adjustment C083 R/W 0 to 65530 1 1458h Not used    1459h Thermistor adjustment C085 R/W 0 to 10000 0.1 145Ah to 145Eh Not used    145Fh Not used   