omron — Extended Function Mode

3-7 Parameter List 3 Operation * 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001 to C008. 3-36 Parameter No. Function name Monitor or data range Default setting Changes during operation Unit Page Others b078 Integrated power clear Cleared with the Enter key after changing to 01 00 Yes  4-4 b079 Integrated power display gain 1. to 1000. 1. No  b082 Starting frequency 0.10 to 9.99 0.50 No Hz 4-64 b083 Carrier frequency 0.5 to 15.0 *Derating enabled 5.0 No kHz 4-65 4-115 b084 Initialization selection 00: Clears the trip monitor 01: Initializes data 02:

Clears the trip monitor and initializes data 00 No  4-66 b085 Initialization parameter selection 00 *Do not change. 00 No  b086 Frequency conversion coefficient 0.1 to 99.0 1.0 Yes  4-2 b087 STOP key selection 00: Enabled 01: Disabled 02: Disabled only during stop 00 No  4-67 b088 Free-run stop selection 00: 0 Hz start 01: Frequency matching start 02: Frequency pull-in restart 00 No  4-68 b089 Automatic carrier reduction 00: Disabled 01: Enabled 00 No  4-70 b090 Usage rate of regenerative braking function 0.0 to 100.0 0.0 No % 4-71 b091 Stop selection 00: Deceleration → Stop 01: Free-run stop 00 No  4-68 b092 Cooling fan control 00: Always ON 01:

ON during RUN 01 No  4-71 b095 Regenerative braking function operation selection 00: Disabled 01: Enabled (Disabled during stop) 02: Enabled (Enabled during stop) 00 No  b096 Regenerative braking function ON level 330 to 380 660 to 760 360/ 720 No V b098 Thermistor selection 00: Disabled 01: PTC enabled 02: NTC enabled 00 No  4-72 b099 Thermistor error level 0. to 9999. 3000. No Ω