3-7 Parameter List 3 Operation * 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001 to C008. 3-35 Parameter No. Function name Monitor or data range Default setting Changes during operation Unit Page Others b060 Window comparator FV upper limit level Set an upper limit level. Setting range: 0 to 100 Lower limit: Lower limit level + Hysteresis width × 2 100. Yes % 4-63 b061 Window comparator FV lower limit level Set a lower limit level. Setting range: 0 to 100 Upper limit: Upper limit level - Hysteresis width × 2 0. Yes % b062 Window comparator FV hysteresis width Set a hysteresis width for the upper and lower limit levels.
Setting range: 0 to 10 Upper limit: (Upper limit level - Lower limit level) × 2 0. Yes % b063 Window comparator FI upper limit level Set an upper limit level. Setting range: 0 to 100 Lower limit: Lower limit level + Hysteresis width × 2 100. Yes % b064 Window comparator FI lower limit level Set a lower limit level. Setting range: 0 to 100 Upper limit: Upper limit level - Hysteresis width × 2 0. Yes % b065 Window comparator FI hysteresis width Set a hysteresis width for the upper and lower limit levels. Setting range: 0 to 10 Upper limit: (Upper limit level - Lower limit level) × 2 0. Yes % b066 Window comparator FE upper limit level Set an upper limit level. Setting range:
-100 to 100 Lower limit: Lower limit level + Hysteresis width × 2 100. Yes % b067 Window comparator FE lower limit level Set a lower limit level. Setting range: -100 to 100 Upper limit: Upper limit level - Hysteresis width × 2 -100. Yes % 4-63 b068 Window comparator FE hysteresis width Set a hysteresis width for the upper and lower limit levels. Setting range: 0 to 10 Upper limit: (Upper limit level - Lower limit level) × 2 0. Yes % b070 Analog operation level at FV disconnection 0. to 100./no (ignored) no No b071 Analog operation level at FI disconnection 0. to 100./no (ignored) no No b072 Analog operation level at FE disconnection -100. to 100./no (ignored) no No