omron — Extended Function Mode

3-7 Parameter List 3 Operation * 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001 to C008. 3-42 Parameter No. Function name Monitor or data range Default setting Changes during operation Unit Page Analog monitor C027 MP selection 00: Output frequency 01: Output current 02: Output torque 03: Digital output frequency 04: Output voltage 05: Input voltage 06: Thermal load rate 07: LAD frequency 08: Digital current monitor 09: Motor temperature 10: Fin temperature 12: Not used 00 No  4-104 4-114 C028 AM selection 00: Output frequency 01: Output current 02: Output torque 04: Output voltage 05: Input voltage 06: Thermal load rate 07:

LAD frequency 09: Motor temperature 10: Fin temperature 11: Output torque 13: Not used 00 No  4-105 4-114 C029 AMI selection 00: Output frequency 01: Output current 02: Output torque 04: Output voltage 05: Input voltage 06: Thermal load rate 07: LAD frequency 09: Motor temperature 10: Fin temperature 14: Not used 00 No  C030 Digital current monitor reference value 0.20 × Rated current to 2.00 × Rated current (Current value at the digital current monitor output 1440 Hz) Rated current Yes A 4-104