3-7 Parameter List 3 Operation * 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001 to C008. 3-45 Parameter No. Function name Monitor or data range Default setting Changes during operation Unit Page Communication function C071 Communication speed selection (Baud rate selection) 02: Loop-back test 03: 2400 bps 04: 4800 bps 05: 9600 bps 06: 19200 bps 04 No 4-137 C072 Communication station No. selection 1. to 32. 1. No C073 Communication bit length selection 7: 7-bit 8: 8-bit 7 No C074 Communication parity selection 00: No parity 01: Even 02: Odd 00 No C075 Communication stop bit selection 1: 1-bit 2:
2-bit 1 No C076 Communication error selection 00: Trip 01: Trip after deceleration stop 02: Ignore 03: Free-run stop 04: Deceleration stop 02 No C077 Communication error timeout 0.00 to 99.99 0.00 No s 4-99 4-137 C078 Communication wait time 0. to 1000. 0. No ms 4-137 C079 Communication method selection 00: ASCII 01: Modbus-RTU 01 No Adjustment C081 FV adjustment 0. to 9999. 1000 to 6553 (10000 to 65530) Factory default Yes C082 FI adjustment 0. to 9999. 1000 to 6553 (10000 to 65530) Factory default Yes C083 FE adjustment 0. to 9999. 1000 to 6553 (10000 to 65530) Factory default Yes C085 Thermistor adjustment 0.0 to 999.9 1000.
Factory default Yes 4-72 C091 Not used Use "00". * Do not change. 00 No Others C101 UP/DWN selection 00: Do not store the frequency data 01: Store the frequency data 00 No 4-87 C102 Reset selection 00: Trip reset at power-on 01: Trip reset when the power is OFF 02: Enabled only during trip (Reset when the power is ON) 03: Trip reset only 00 Yes 4-84 4-128 C103 Reset frequency matching selection 00: 0 Hz start 01: Frequency matching start 02: Frequency pull-in restart 00 No 4-84