4.4 Start-up Flowcharts ◆ Flowchart A: Basic Start-Up and Motor Tuning Figure 4.6 , Flowchart A, describes basic start-up sequence for the drive and motor system. This sequence varies slightly depending on application. Use drive default parameter settings in simple applications that do not require high precision. Figure 4.6 START Install and wire the drive as explained in Chapters 1, 2 and 3 . Start-Up Programming & Operation Apply main power on to the drive. Adhere to safety messages concerning application of power. Application Presets A1-06 used? Yes Set the control mode in parameter A1-02. For information about the control modes refer to section 4.5.
Refer to section 4.4 Application Macros Set the basic parameters: b1-01/02 for frequency reference and Run command source H1- , H2- , H3- , H4- and H6- for I/O terminal functions settings d1- for multi-speed references if used C1- and C2- for accel./decel. and S-curve time settings C6-01 for heavy/normal duty mode selection L3-04 if a braking option is used No TO 4 0: V/f control 5: Open Loop Vector for PM motors Control Mode A1-02 = 2: Open Loop Vector control To Flowchart A-1 To Flowchart A-2 To Flowchart A-3 From Flowchart A-1, A-2, or A-3 Run the motor without load, check the rotation direction and operation.
Verify, external signal commands to the drive work as desired. Couple the load or machine to the motor. Run the machine and check it operates as desired Fine tune parameters. Adjust application settings (PID, ...) if necessary. Check machine operation and verify parameter settings. Drive is ready to run the application. Figure 4.6 Basic Start-Up and Motor Tuning OYMC TOEP C71060622-01-OY V1000 User Manual 103 )5 20