4.4 Start-up Flowcharts ◆ Subchart A1: Simple Motor Set-Up with Energy Savings or Speed Search using V/f Mode Figure 4.7 , Flowchart A1, describes simple motor set-up for V/f control. V/f Motor Control is suited for the most basic applications such as fans or pumps. This procedure illustrates using Energy Savings and Speed Estimation Speed Search. V/f control can be used where rotational auto-tuning cannot be performed. Figure 4.7 From Flowchart A Set or verify the V/f pattern settings E1- . Energy Savings (b6-01 = 1) or Speed Estimation Speed Search (b3-24 = 1) enabled? Is the motor cable longer than 50 m? Perform Rotational Auto-Tuning for V/f Control.