4.4 Start-up Flowcharts ◆ Subchart A2: High Performance Operation Using Open Loop Vector Motor Control Figure 4.8 , Flowchart A2, uses Open Loop Vector Control for high-performance motor operation. This is appropriate for applications requiring high starting torque, torque limits, and improved speed regulation. Figure 4.8 From Flowchart A Start-Up Programming & Operation NO YES Possible for motor to rotate during tuning? * NO * Rotational tuning should be performed with the load disconnected 4 Motor test report/ data sheet available? YES Enter the data from the motor data sheet to E2- parameters. Calculate necessary E2- parameter data using the name plate information. .
Perform Rotating Auto- Tuning (T1-01 = 0) YES Is the motor cable longer than 50 m? NO Perform Stationary Auto-Tuning for terminal resistance (T1-01 = 2) Return to Flowchart A Figure 4.8 Flowchart A2: High Performance Operation Using Open Loop Vector Motor Control OYMC TOEP C71060622-01-OY V1000 User Manual 105