4.5 Application Presets WARNING! Confirm the drive I/O signals and external sequence before starting test run. Setting parameter A1-06 may change the I/O terminal function automatically from the factory setting. Failure to comply may result in death or serious injury. Perform a 2-wire or 3-wire initialization (A1-03 = 2220 or 3330) on the drive before selecting one of the application presets or before switching between application presets. The initialization process should reset drive parameters before using an application preset. Save user-edited parameters to a list by setting o2-03 to “1”.
This allows for more immediate access a specific list of relevant parameters and saves time scrolling through the parameter menu items. Set the parameter access level for Preferred Parameters (A1-01 = “1”) to display only the setup parameters. The parameters listed in the table below are unaffected by drive initialization: The control method set to A1-02 is unaffected when performing a 2-wire or 3-wire initialization, but it automatically changes according to the value set to parameter A1-06. ■ Related Parameters 108 OYMC TOEP C71060622-01-OY V1000 User Manual No.
Parameter Name A1-02 Control Method Selection C6-01 Duty Selection E1-03 V/f Pattern Selection E5-01 Motor Code Selection (for PM motors) o2-04 Drive Unit Selection No. Parameter Name Setting Range Default A1-01 Access Level Selection 0: Operation only 1: User Parameters (access to a set of parameters selected by the user) 2: Advanced Access Level 2 A1-03 Initialize Parameters 0: No Initialize 1110: User Initialize (The user must first set user parameter values and then store them using parameter o2-03) 2220: 2-Wire Initialization 3330: 3-Wire Initialization 4440: FBD’s Initialization 5550: OPE04 Error Reset 0 A2-02 to A2-32 User Parameters, 2 to 32 b1-01 to o2-08