omron — Application Presets: A1-06

4.5 Application Presets Default setting value is dependent on parameter A1-06, Application Selection Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 does not = 0. Start-Up Programming & Operation ■ Application Presets Below is a list of application presets and the values automatically assigned to the parameters as a result of each preset: A1-06 = 1 - Water Supply Pump Application Table 4.5 Parameters and Settings 4 Table 4.6 Parameters Automatically Saved as Preferred (A2-01 to A2-16) OYMC TOEP C71060622-01-OY V1000 User Manual 109 No. Parameter Name Setting Range Default A2-33 User Parameter Automatic Selection 0:

Parameters A2-01 through A2-32 are reserved for the user to create a list of User Parameters. 1: Save history of recently viewed parameters. Recently edited parameters will be saved to A2-17 through A2-32 for quick access. 1 o2-03 User Parameter Default Value 0: No Change 1: Set Defaults - Saves current parameter settings as user initialization. 2: Clear All - Clears the currently saved user initialization. 0 No. Parameter Name Optimum Setting A1-02 Control Method Selection 0: V/f Control b1-04 Reverse Operation Selection 1: Reverse prohibited C1-01 Acceleration Time 1 1.0 s C1-02 Deceleration Time 1 1.0 s C6-01 Duty Rating 1:

Normal Duty E1-03 V/f Pattern Selection 0FH E1-07 Mid Output Frequency 30.0 E1-08 Mid Output Frequency Voltage 50.0 L2-01 Momentary Power Loss Operation Selection 1: Enabled L3-04 Stall Prevention Selection during Deceleration 1: Enabled No. Parameter Name No. Parameter Name b1-01 Frequency Reference Selection E1-08 Mid Output Frequency Voltage b1-02 Run Command Selection E2-01 Motor Rated Current b1-04 Reverse Operation Selection H1-05 Multi-Function Digital Input Terminal S5 Function Selection C1-01 Acceleration Time 1 H1-06 Multi-Function Digital Input Terminal S6 Function Selection C1-02 Deceleration Time 1