omron — Application Presets: A1-06

4.5 Application Presets A1-06 = 4: HVAC Fan Table 4.11 Parameters and Settings Start-Up Programming & Operation 4 Table 4.12 Parameters Automatically Saved as Preferred (A2-01 to A2-16) OYMC TOEP C71060622-01-OY V1000 User Manual 111 No. Parameter Name No. Parameter Name b1-04 Reverse Operation Selection E2-01 Motor Rated Current b3-01 Speed Search Selection at Start H1-05 Multi-Function Digital Input Terminal S5 Function Selection C1-01 Acceleration Time 1 H1-06 Multi-Function Digital Input Terminal S6 Function Selection C1-02 Deceleration Time 1 L5-01 Number of Auto Restart Attempts E1-03 V/f Pattern Selection No. Parameter Name Optimum Setting A1-02 Control Method Selection 0:

V/f Control b1-04 Reverse Operation Selection 1: Reverse prohibited C6-01 Duty Rating 1: Normal Duty C6-02 Carrier Frequency Selection 3: 8.0 kHz H2-03 Terminals P2 Function Selection (open-collector) 39: Watt Hour Pulse Output L2-01 Momentary Power Loss Operation Selection 2: CPU Power Active - Drive will restart if power returns prior to control power supply shut down. L8-03 Overheat Pre-Alarm Operation Selection 4: Derated operation L8-38 Carrier Frequency Reduction 2: Carrier frequency derating across entire frequency range. No. Parameter Name No.

Parameter Name b1-01 Frequency Reference Selection E1-03 V/f Pattern Selection b1-02 Run Command Selection E1-04 Max Output Frequency b1-04 Reverse Operation Selection E2-01 Motor Rated Current C1-01 Acceleration Time 1 H3-11 Terminal A2 Gain Setting C1-02 Deceleration Time 1 H3-12 Frequency Reference (Current) Terminal A2 Input Bias C6-02 Carrier Frequency Selection L2-01 Momentary Power Loss Operation Selection d2-01 Frequency Reference Upper Limit L8-03 Overheat Pre-Alarm Operation Selection d2-02 Frequency Reference Lower Limit o4-12 kWH Monitor Initial Value Selection