omron — Application Presets: A1-06

4.5 Application Presets A1-06 = 5: Compressor Application Table 4.13 Parameters and Settings Table 4.14 Parameters Automatically Saved as Preferred (A2-01 to A2-16) A1-06 = 6: Hoist Application Table 4.15 Parameters and Settings 112 OYMC TOEP C71060622-01-OY V1000 User Manual No. Parameter Name Optimum Setting A1-02 Control Method Selection 0: V/f Control b1-04 Reverse Operation Selection 1: Reverse prohibited C1-01 Acceleration Time 1 5.0 s C1-02 Deceleration Time 1 5.0 s C6-01 Duty Rating 0: Heavy Duty E1-03 V/f Pattern Selection 0FH L2-01 Momentary Power Loss Operation Selection 1: Enabled L3-04 Stall Prevention Selection during Deceleration 1: Enabled No. Parameter Name No.

Parameter Name b1-01 Frequency Reference Selection E1-03 V/f Pattern Selection b1-02 Run Command Selection E1-07 Mid Output Frequency b1-04 Reverse Operation Selection E1-08 Mid Output Frequency Voltage C1-01 Acceleration Time 1 E2-01 Motor Rated Current C1-02 Deceleration Time 1 No. Parameter Name Optimum Setting A1-02 Control Method Selection 2: Open Loop Vector Control b1-01 Frequency Reference Selection 0: Operator b6-01 Dwell Reference at Start 3.0 Hz b6-02 Dwell Time at Start 0.3 s C1-01 Acceleration Time 1 3.0 s C1-02 Deceleration Time 1 3.0 s C6-01 Duty Rating 0: Heavy Duty C6-02 Carrier Frequency Selection 2:

5 kHz d1-01 Frequency Reference 1 6.0 Hz d1-02 Frequency Reference 2 30.0 Hz d1-03 Frequency Reference 3 50.0 Hz E1-03 V/f Pattern Selection 0FH H2-02 Terminals P1 Function Selection (open-collector) 37: During frequency output