omron — Frequency Reference Source: b1-01

4.6 Basic Drive Setup Adjustments Figure 4.12 Figure 4.12 Voltage Input for the Main Frequency Reference Control Circuit Terminal A2 (Voltage/Current Input): Start-Up Programming & Operation Use control circuit Terminal A2 when supplying the frequency reference with a current signal between 4 to 20 mA. Use control circuit Terminal A1 for supplying a voltage reference. • Set the signal level for analog input A2 to current input (H3-09 = “2” for 4 to 20 mA, H3- 09 = “3” for 0 to 20 mA). • Set the function for analog input A2 to frequency reference (H3-10 = “0”) to command terminal A2 to be a frequency reference. • Set DIP switch S1 to the I position for a current signal input.

4 Figure 4.13 Figure 4.13 Current Input for the Main Speed Reference To configure the frequency reference to switch between analog input A1 and A2 (main/aux frequency switch), use the following setup: Switching between Main/Auxiliary Frequency References 1. Set the frequency reference source to terminals (b1-01 = “1”). 2. Set one of the digital inputs to auxiliary reference 1, H1- …… = “3” (preset for terminal S5). 3. Set input signal type of terminal A2 using dip switch S1 and parameter H3-09. 4. Set the function of analog input A2 to Auxiliary frequency (H3-10 = “3”).

OYMC TOEP C71060622-01-OY V1000 User Manual 121 0 to 10 V 2 kΩ Drive 㧗V (+10.5 V㧘20 mA) A1 Main Frequency Reference (voltage input) A2 Auxiliary Frequency Reference (voltage/current input) AC Frequency Reference Common DIP switch S1 Drive V I 㧗V (+10.5 V, 20 mA) A1 Main Frequency Reference (voltage input) (0) 4 - 20 mA input A2 Main Frequency Reference (current input) AC Frequency Reference Common Drive 㧗V (+10.5 V, 20 mA) A1 Main Frequency Reference (voltage input) A2 Main Frequency Reference (current input) AC Frequency Reference Common