4.6 Basic Drive Setup Adjustments ◆ FBD’s Function Selection: A1-07 FBD’ programmability can be used to customize the drive functionality or add PLC functionality by the interconnection and configuration of basic software function blocks. The drive performs the so created program in a cycle of 2 ms. Parameter A1-07 can be used to enable or disable the FBD’s program inside the drive. Setting A1-07 to “0” disables the FBD’s program in the drive. Setting A1-07 to “1” enables the FBD’s program in the drive. If A1-07 is set to “2” a digital input (H1- …… = “9F”) can be used to enable or disable FBD’s. FBD’s will be enabled if the input is off. Set A1-07 to “0” when FBD’s is not used.
If FBD’s assigned functions to any multi-function output terminals, those functions stay set after disabling FBD’s. ◆ Frequency Reference Source: b1-01 This section explains how to assign the frequency reference. Parameters b1-01 and b1-02 can be used to select the source of the run command and the frequency reference independently, e.g., set the reference from the operator and set the run command from the terminals. ■ Frequency Reference from the LED Operator: b1-01 = 0 When b1-01 = 0 the frequency reference will be provided by the LED operator. Refer to The Drive and Programming Mode on page 93 for information on how to set the frequency reference.
■ Frequency Reference from the Analog Input Terminal: b1-01 = 1 When b1-01 = 1, analog inputs A1 and A2 provide the frequency reference. Note: Set H3-02 (Terminal A1 Function Selection) to “0” to configure Terminal A1 for the main analog frequency reference. Using a Single Analog Signal (V or I) as the Frequency Reference When entering the main frequency reference with a voltage signal, use the voltage input set up in control circuit terminal A1. Control Circuit Terminal A1 (Voltage Input): 120 OYMC TOEP C71060622-01-OY V1000 User Manual No. Parameter Name Setting range Default A1-07 FBD’s Function Selection 0: Disabled 1: Enabled 2: Terminal input switch (requires that H1- = 9F) 0