4.6 Basic Drive Setup Adjustments 3330: 3-Wire Initialization Returns all parameters to factory default values for 3-wire control. 1110: User Initialization Returns all parameters to backed-up values stored at the time the user set o2-03 = 1 and pressed enter to back-up parameter settings. 5550: Uploads Parameter Data from the Removable Control Circuit Terminal Board Replacing either the removable control circuit terminal board or the drive and applying main power may result in an oPE04 fault. If parameter setting data in the removable control circuit terminal board is correct, set A1-03 to “5550” to upload the data to the drive. Start-Up Programming & Operation Note:
Refer to Run Command Input Selection: b1-02 on page 123 , for more information on a 2-wire and 3-wire sequence. Note: Initializing the drive for 2-wire sequence (A1-03 = 2220) returns all drive parameters to factory settings. Back up all parameters in the event of accidental initialization. the data with 2-wire sequence returns all the set parameters to the factory settings. Refer to Backing Up Parameter Values: o2-03 on page 160 . ◆ Application Presets: A1-06 4 The drive features application presets to facilitate the set up of commonly used applications such as a water supply pump, conveyor, exhaust fan, HVAC fan, compressor, hoist, and travelling application.
Selecting one of these presets automatically sets the required parameters to the optimum values and changes the appropriate I/O terminal settings for that specific application. Refer to Application Presets on page 107 Verify all I/O signals and external sequences before operating the motor. Refer to Hoist Application Preset Specifics on page 115 when selecting a hoist application. Users are able to make further adjustments to these settings using the Setup Mode. All general-purpose parameters are accessible when A1-06 = 0. OYMC TOEP C71060622-01-OY V1000 User Manual 119 No. Parameter Name Setting Range Default A1-06 Application Presets 0: General-purpose (A2 parameters are not affected) 1:
Water supply pump 2: Conveyor 3: Exhaust fan 4: HVAC fan 5: Air compressor 6: Hoist 7: Travelling application 0