omron — Stopping Method Selection: b1-03

4.6 Basic Drive Setup Adjustments Figure 4.16 Figure 4.16 Example Wiring Diagram for 3-Wire Sequence Using Terminal S5 Start-Up Programming & Operation WARNING! When 3-Wire sequence is used, set the drive to 3-Wire sequence before wiring the control terminals and ensure parameter b1-17 is set to 0 (drive does not accept a run command at power up (default)). If the drive is wired for 3-Wire sequence but set up for 2-Wire sequence (default) and if parameter b1-17 is set to 1 (drive accepts a Run command at power up), the motor will rotate in reverse direction at power up of the drive and may cause injury. Note: When terminal S5 is open, the motor rotates forward.

When closed, the motor rotates in reverse. Note: Refer to Parameter List on page 293 for a list of digital input functions. After performing a 3- wire initialization (A1-03 = “3”), the drive will automatically assign the forward/reverse command to terminal S5. 4 CAUTION! The motor will begin rotating as soon as the power is switched on. Proper precautions must be taken to ensure that the area around the motor is safe prior to powering up the drive. Failure to do so may result in minor or moderate injury. Note: Run by Turning on/off the Power Supply. For safety reasons, the drive is initially set up not to accept a run command at power up (b1-17 = "0").

If a run command is issued at power up, the RUN indicator LED will flash quickly. To change this and have the run command issued by the drive, change parameter b1-17 to 1 ◆ Stopping Method Selection: b1-03 When a Stop command is issued, the drive stops the motor using one of four possible methods. When b1-03 = 0, the motor will decelerate to a stop when a stop command is entered. The deceleration time is set by C1-02 (Deceleration Time 1). Refer to Acceleration/ Deceleration: C1-01 to C1-11 on page 128 . ■ Ramp to Stop:

b1-03 = 0 When the output frequency falls below the DC Injection braking start frequency (b2-01) during deceleration, the DC Injection braking current (b2-02) will be activated for the specified DC Injection time at stop (b2-04). OYMC TOEP C71060622-01-OY V1000 User Manual 125 Stop Switch Run Switch Drive (N.C.) (N.O.) S1 Run Command (runs when open) S2 Stop Command (stops when closed) S5 FWD/REV Command (multi-function input)* SC Digital Input Common Run Command (runs when open) Stop Command (stops when closed) FWD/REV Command (multi-function input)* Digital Input Common