4.6 Basic Drive Setup Adjustments Figure 4.17 Note: Parameter b2-04 is not available if using PM Open Loop Vector. Instead, set the Short Circuit Braking time to b2-13. Figure 4.17 Ramp to Stop ■ Coast to Stop: b1-03 = 1 When the run command is removed, the drive will shut off its output and the motor will coast (uncontrolled deceleration). The motor will coast to a stop at the rate determined by the load inertia. Figure 4.18 Run Command ON OFF Output Voltage Drive output voltage interrupted Motor Rotations Figure 4.18 Coast to Stop Note: 1. After entering a stop command, the drive will not accept another run command until the time set to L2- 03 (Minimum Baseblock Time) passes. 2.
Do not enter another run command until the motor comes to a complete stop. If a run command must be entered before the motor has fully stopped, use DC Injection or Speed Search functions to slow the motor or catch the motor before restarting. DC Injection Braking stops a coasting motor without regenerative operation. When the run command is removed, the drive will baseblock (turn off its output) for the minimum ■ DC Injection Braking to Stop:
b1-03 = 2 126 OYMC TOEP C71060622-01-OY V1000 User Manual Run Command ON OFF Output Frequency Decelerates according to the specified deceleration time Zero Speed Level (b2-01) Decel Time (C1-02, etc.) DC Injection Current (b2-02) DC Injection Braking D C B raking T im e at S top (b2-04) Zero Speed Level (b2-01) Decel Time (C1-02, etc.) DC Injection Current (b2-02) DC Injection Current (b2-02) D C B raking T im e at S top (b2-04)