omron — Stopping Method Selection: b1-03

4.6 Basic Drive Setup Adjustments baseblock time (L2-03). Once the minimum baseblock time has expired, the drive will inject DC current into the motor windings to lock the motor shaft. The stopping time will be reduced as compared to coast to stop. The level of DC Injection current is set by parameter b2-02 (default = 50%). The time for DC Injection Braking is determined by the value set to b2-04 and by the output frequency at the time the run command is removed. Note: DC Injection braking cannot be selected as a stopping method in PM Open Loop Vector Control.

Figure 4.19 Run Command ON OFF Output Frequency Minimum Baseblock Time Start-Up Programming & Operation DC Injection Braking Motor Speed 4 DC Injection Braking Time b2-04 x 10 b2-04 Output frequency when stop command was entered 100% (Max Output Frequency) 10% Figure 4.19 DC Injection Braking Stop *See Figure 4.18 Note: Extend baseblock time (L2-03) if overcurrent (OC) occurs on stop command input. ■ Coast to Stop with Timer: Ignoring a Run Command Input within the Deceleration Time: b1-03 = 3 When b1-03 = 3, a stop command interrupts drive output and the motor coasts to stop. The drive will not accept the next run command until time “t” has passed.

Time “t” is determined by the output frequency at the moment the stop command was entered and the deceleration time set to the drive according to Figure 4.20 . OYMC TOEP C71060622-01-OY V1000 User Manual 127 DC Inj.Braking time at Stop (b2-04)*