4.6 Basic Drive Setup Adjustments Figure 4.20 Run Command Output Frequency ON ON ON OFF OFF Drive output voltage interrupted Operation Wait Time t Deceleration time (C1-02, etc.) Operation wait time t Minimum Baseblock Time 㧔 L2-03 㧕 Output frequency when stop command was entered Minimum Output Frequency 100 㧑 (Max Output Frequency) Figure 4.20 Coast to Stop with Timer ◆ Acceleration/Deceleration: C1-01 to C1-11 C1-01 (Acceleration Time 1) sets the time to accelerate from 0 to the maximum output frequency (E1-04). C1-02 (Deceleration Time 1) sets the time to decelerate from maximum output frequency to 0. The parameter can be changed during run. WARNING! Sudden Movement Hazard.
Rapid deceleration may cause the drive to fault on an overvoltage condition, resulting in death or serious injury due to an uncontrolled motor state. Set an acceptable deceleration time in parameter C1-09 when using the Fast-stop feature. 128 OYMC TOEP C71060622-01-OY V1000 User Manual No. Parameter Name Description Setting Range Default C1-01 Acceleration Time 1 Sets the time to accelerate from 0 to 100% (maximum output frequency). 0.0 to 6000.0 10.0 s C1-02 Deceleration Time 1 Sets the time to decelerate from 100% (maximum output frequency) to 0%. C1-10 Accel/Decel Time Setting Units Sets the setting resolution of C1-01 toC1-09. 0: 0.01 s (0.00 to 600.00 s) 1:
0.1 s (0.0 to 6000.0 s) 0, 1 1