omron — Acceleration/Deceleration: C1-01 to C1-11

4.6 Basic Drive Setup Adjustments ■ Accel/Decel Time Setting Units Set the units for the acceleration and deceleration times using parameter C1-10 (default = 1). Up to four different acceleration / deceleration times can be selected using any two digital input terminals S1 through S6. ■ Switching Accel/Decel Times with Digital Input Terminals Start-Up Programming & Operation Program two parameters H1-01 through H1-06 to “07” (Accel/Decel Time 1) and “1A” (Accel/Decel Time 2). The combination of these two inputs activates the acceleration/ deceleration times as shown below.

As the contacts of the terminals open and close, the following acceleration and deceleration time combinations are possible: 4 ■ Automatically Switching Acceleration/Deceleration Times The drive can automatically switch between acceleration and deceleration times. When the output frequency reaches the value set to C1-11, the drive will switch acceleration and deceleration times as shown in the figure below. Setting C1-11 to 0.0 Hz disables this function.

Figure 4.21 Output Frequency C1-11 Accel/Decel Time Switch Frequency C1-07 setting C1-01 setting C1-02 setting C1-08 setting When the output frequency ҈ C1-11, drive uses Accel/Decel Time 1 (C1-01, -02) When the output frequency C1-11, drive uses Accel/Decel Time 2 (C1-07, -08) Figure 4.21 Accel/Decel Time Switching Frequency OYMC TOEP C71060622-01-OY V1000 User Manual 129 Setting Description 0 Time is set in units of 0.01 s, making the setting range 0.00 to 600.00 seconds. 1 Time is set in units of 0.1 s, making the setting range 0.0 to 6000.0 seconds.

Accel/Decel Time 1 H1- = 7 Accel/Decel Time 2 H1- = 1A Acceleration Time Deceleration Time Open (not selected) Open (not selected) C1-01 C1-02 Closed Open (not selected) C1-03 C1-04 Open (not selected) Closed C1-05 C1-06 Closed Closed C1-07 C1-08