4.6 Basic Drive Setup Adjustments Start-Up Programming & Operation 4 Note: By selecting HD/ND motor parameters E2 and E4 are changed to values for the maximum applicable motors. ■ Carrier Frequency Selection: C6-02 Fixed Carrier Frequencies The carrier frequency can be set using parameter C6-02 as shown in table below. Note: Settings 7 through A for parameter C6-02 use a Swing PWM equivalent to a 2 kHz audible noise. This function turns the motor noise into a less obtrusive white noise. Note: The upper limit for the carrier frequency is determined by drive capacity.
OYMC TOEP C71060622-01-OY V1000 User Manual 131 Mode Heavy Duty Rating Normal Duty Rating Characteristics Overload 150 % Rated Load 100 % 0 Motor Speed 100 % 120 % Overload Rated Load 100 % 0 Motor Speed 100 % Application Use HD Rating is designed applications requiring a high overload tolerance with constant load torque. Such applications include extruders, conveyors and cranes. Use ND Rating for applications in which the torque requirements drop along with the speed. Examples include fans or pumps where a high overload tolerance is not required.
Overload capability (OL2) 100% continuous, 150% of drive rated current for 60 s 100% continuous, 120% of drive rated current for 60 s L3-02 Stall Prevention during Acceleration 150% 120% L3-06 Stall Prevention during Run 150% 120% Overload 150 % Rated Load 100 % 0 Motor Speed 100 % Overload Rated Load Rated Load Parameter Name Description Setting Range Default C6-02 Carrier frequency 1: 2.0 kHz 2: 5.0 kHz 3: 8.0 kHz 4: 10.0 kHz 5: 12.5 kHz 6: 15.0 kHz 7: Swing PWM1 8: Swing PWM2 9: Swing PWM3 A: Swing PWM4 F: User defined (C6-03 to C6-05) 1 to F depends on drive size