omron — Drive Input Voltage Setting: E1-01

4.6 Basic Drive Setup Adjustments A carrier frequency setup error (oPE11) will occur when carrier frequency gain (C6-05) is greater than 6 and C6-03 Carrier Frequency Setting Error (oPE11) Note: Refer to Troubleshooting without Fault Display on page 224 for information on operator errors (oPE). The drives rated output current depends on the carrier frequency selection. If the carrier frequency is increased beyond the default setting, the output current is derated like explained in Carrier Frequency Derating on page 290 . The overload capability will be 120/150 % of the derated output current for 60 s (Normal Duty/ Heavy Duty).

■ Carrier Frequency and Output Current Derating Start-Up Programming & Operation ◆ Drive Input Voltage Setting: E1-01 Set E1-01 according to the power supply voltage. This setting serves as a base value for certain drive protective functions. NOTICE: Set drive input voltage (not motor voltage) in parameter E1-01 for proper function of the protective features of the drive. Failure to comply could result in improper drive operation. Set parameter E1-01 to match the input voltage of the drive. 4 The default depends on the voltage class and must be doubled for 400V class drives.

The input voltage level determines the overvoltage detection level, the Kinetic Energy Backup operation voltage and the operation level of the braking transistor as shown in the table below. ■ Input Voltage Setting Value: E1-01 OYMC TOEP C71060622-01-OY V1000 User Manual 133 Parameter Name Description Setting Range Default E1-01 Input Voltage Setting Set to the nominal voltage of the incoming line. Sets the maximum and base voltage used by preset V/f patterns (E1-03), and adjusts the levels of drive protective features (e.g., overvoltage, braking resistor level, stall prevention, etc.). 200 V Class: 155 to 255 400 V Class:

310 to 510 200 V Voltage Setting Value of E1-01 (Approximate Values) OV Detection Level Braking Transistor Operation Level UV Detection Level Desired AC Voltage during KEB Voltage Level for OV Suppression, Stall Prevention 200 V Class all settings 410 V 394 V 190 V (single-phase=160 V) 240 V 370 V 400 V Class setting ≥ 400 V 820 V 788 V 380 V 480 V 740 V setting 740 V 708 V 350 V 440 V 660 V