4.6 Basic Drive Setup Adjustments Note: The braking transistor operation levels are for the drives internal braking chopper.If an external CDBR braking chopper is used refer to the instruction manual “Dynamic Braking Resistor Unit for VARISPEED-600 Series, TOBPC72060000” ◆ V/f Pattern Selection: E1-03 Parameter E1-03 is only available when using V/f Control. It allows the user to set the required V/f pattern and drive output voltage. When running a high-speed or special-purpose motor, this function fine tunes the amount of torque required for the load. Select the V/f pattern from 15 fixed V/f patterns or 1 user-programmable V/f pattern. ■ Setting Instructions for Setting a V/f Pattern 1.
Set the input voltage for the drive. Refer to Drive Input Voltage Setting: E1-01 on page 133 . 2. Set the V/f pattern by: • * choosing one of the 15 preset V/f patterns (setting = 0 through E) • ** select the Custom V/f pattern (setting = F, default setting) 3. In case of * the parameters listed below are automatically set. Refer to Selecting a Preset V/f Pattern on page 135 In case of **, the parameters listed below are adjustable. Figure 4.24 Output Voltage (V) E1-05 E1-12 E1-13 E1-08 E1-10 E1-09 E1-07 E1-06 E1-11 E1-04 Figure 4.24 V/f Pattern Frequency (Hz) 134 OYMC TOEP C71060622-01-OY V1000 User Manual No.
Parameter Name Description Setting Range Default E1-03 V/f Pattern Selection 0 to E: Select from 15 preset V/f patterns. F: Custom V/f pattern (allows use of E1-04 through E1-10). 0 to F F No. Parameter Name E1-04 Maximum Output Frequency E1-05 Maximum Voltage E1-06 Base Frequency E1-07 Mid Output Frequency No. Parameter Name E1-08 Mid Output Frequency Voltage E1-09 Minimum Output Frequency E1-10 Minimum Output Frequency Voltage