4.6 Basic Drive Setup Adjustments ■ Selecting a Preset V/f Pattern By setting parameter E1-03 between 0 and E, the V/f patterns below can be selected. Table 4.19 V/f Patterns Start-Up Programming & Operation 4 ■ V/f Pattern Characteristics These graphs apply to 200 V class drives; double the values for 400 V class drives. • Constant Torque Characteristics, Settings 0 through 3 OYMC TOEP C71060622-01-OY V1000 User Manual 135 Setting Specification Characteristic Application 0 (F) 50 Hz Constant torque For general purpose applications, torque remains constant regardless of speed changes.
1 60 Hz 2 60 Hz (with 50 Hz base) 3 72 Hz (with 60 Hz base) 4 50 Hz, Heavy Duty 3 Reduced or variable torque For applications where torque changes with the speed like fans, pumps, and others that require reduced torque relative to the load. 5 50 Hz, Heavy Duty 2 6 60 Hz, Heavy Duty 3 7 60 Hz, Heavy Duty 2 8 50 Hz, mid starting torque High starting torque • High starting should be selected only when:
• Wiring between the drive and motor exceeds 150 m • Large amount of starting torque is required • AC reactor is installed 9 50 Hz, high starting torque A 60 Hz, mid starting torque B 60 Hz, high starting torque C 90 Hz (with 60 Hz base) Constant output When operating at speeds greater than 60 Hz motor requires constant voltage. Above 60 Hz, motor operates in constant power range. D 120 Hz (with 60 Hz base) E 180 Hz (with 60 Hz base) Setting = 0 50 Hz Setting = 1 60 Hz Setting = 2 60 Hz Setting = 3 72 Hz