omron — Motor Protection: L1-01 and L1-02

4.6 Basic Drive Setup Adjustments 2. Set the proper motor protection level to L1-01. The ability of the cooling fan to keep an induction motor cool varies by the speed control range. Protection characteristics of the electronic thermal overload protection should be set accordingly. Refer to Table 4.20 for motor types and overload tolerances. NOTICE: When connecting multiple motors to one drive, disable the electronic overload protection of the drive (L1-01 = 0) and protect each motor with its own motor thermal overload. Failure to comply could result in improper drive operation. NOTICE: Inadequate motor protection could result in damage to the motor.

Configure a motor thermal overload to disconnect main power to the drive when tripped. When using a thermal relay, disable the motor protection function (L1-01 = “0”). Start-Up Programming & Operation 3. Set the motor overcurrent alarm warning level. When H2-01, H2-02, and H2-03 (Terminal MA, MB, and MC Function selection, Terminal P1 Function Selection, and Terminal P2 Function Selection) are set to 1F motor overload (OL1 alarm warning), a motor overload alarm is enabled. If the electronic thermal value exceeds 90% of the overload detection level, the set output terminal turns on.

Table 4.20 Motor Type and Overload Tolerances 4 OYMC TOEP C71060622-01-OY V1000 User Manual 143 L1-01 Setting Motor Type Overload Tolerance Cooling Fan Capacity Electrothermal Protection (100% motor overload) 1 General- purpose motor (standard motor) 150 Rated Speed = 100% Speed 60 seconds 100 90 Torque (%) 60 50 Continuous A B C 0 5 33 100120 167 200 㧔60Hz㧕 General purpose motors are designed to operate from line power. The most effective cooling occurs when running at line power specifications. Operating continuously at less than line power frequency can trigger motor overload protection (OL1). A fault is then output and the motor will coast to stop.