4.6 Basic Drive Setup Adjustments need for an external overload device. When multiple motors are used with a single drive, separate overload devices are required to properly protect the individual motor branches. Related Parameters Note: Executing C6-01 (Duty mode) changes motor parameters E2 and E4 including motor rated current to the values of the maximum applicable motor. Digital Outputs (H2-01 through H2-03) Setting Procedure 1. Set E2-01 (Motor Rated Current) and E4-01 (Motor 2 Rated Current) to the motor rated current. Note: 1. Values set for the current become the base current for electronic thermal overload protection. 2. These values are automatically set by performing Auto-Tuning.
3. The E4-01 setting is not needed if not using motor 2. 142 OYMC TOEP C71060622-01-OY V1000 User Manual No. Parameter Name Description Setting Range Default Setting E2-01 Motor Rated Current Sets the motor nameplate full load current in amperes (A). This set value becomes the reference value for motor protection, torque limit, and torque control. This value is automatically set during Auto-Tuning. 10 to 200% of drive rated current Less than 11 kW: 2 digits below the decimal point, 11 kW or more: 1 digit below the decimal point. Determined by o2-04 and C6-01 E4-01 Motor 2 Rated Current Sets the motor 2 name plate full load current in amperes (A).
This set value becomes the reference value for motor protection, torque limit, and torque control. This value is automatically set during Auto-Tuning. 10 to 200% of drive rated current Determined by o2-04 and C6-01 L1-01 Motor Overload Protection Selection Enables or disables motor thermal overload protection (OL1) 0: Disabled 1: Protection for general purpose motor 2: Protection for inverter motor 3: Protection for vector motor 4: Protection for PM variable torque motor 0 to 4 1 Use L1-13 (Continuous Electrothermal Operation Selection) to select whether electronic thermal value is “held” or “not held” when the power supply is turned off.
When connecting several motors to one drive, set “0” (disabled) and install a thermal relay on each motor. L1-02 Motor Overload Protection Time Sets the electronic thermal overload protection detection time in the motor overload protection (OL1) function. This setting rarely needs to be changed and should be set in accordance with the overload tolerance of the motor. 0.1 to 5.0 1.0 min Setting Function Description 1F Motor Overload OL1 Alarm Warning (including OH3) Closed = When OL1 function is at 90% of its trip point or greater.