4.6 Basic Drive Setup Adjustments Adjusting the Analog Output Terminal Voltage with H4-02 and H4-03 Note: This example continues from Step 3 in the previous example. Start-Up Programming & Operation 4 Figure 4.26 Analog Output Voltage Gain = Analog output level at 100 % Monitor Value 10 V Output = x 10 V Gain (%) 100 Bias = Analog output level at 0 % Monitor Value (max. 10 V) Output = x 10 V Bias (%) 100 100% 0% 0 V Monitor Contents Figure 4.26 Adjusting the Monitor Output ◆ Motor Protection: L1-01 and L1-02 This section explains how to set motor overload protection.
■ Electronic Thermal Motor Protection The drive has built-in electronic thermal overload protection to detect overload conditions. This protection meets standards set by UL and cUL for motor thermal overload protection. The protective feature is activated when the output current rises above the motor rated current for a specified time. This speed sensitive protective feature interrupts the motor current to protect the motor wiring and windings in the event of overload, eliminating the OYMC TOEP C71060622-01-OY V1000 User Manual 141 Step Display/Result 9. Press the key until back at the Top Screen. ⇒ Step Display/Result 1. Select H4-02 or H4-03 by pressing the and keys.
⇒ Press the key while the drive is stopped.During the 2. display of H4-02 and H4-03 an adjustment voltage signal equal to the current bias or gain setting is output at terminal AM. Use this output signal and adjust the output gain (H4-02) and output bias (H4-03) as required. ⇒