omron — Analog Outputs: H4-01 to H4-03

4.6 Basic Drive Setup Adjustments The parameter can be changed during run. The following example illustrates how to program analog output terminal FM to generate a signal proportional to drive output current (monitor U1-03). ■ Changing Analog Output Settings Using H4-01 to Display Monitor Contents 140 OYMC TOEP C71060622-01-OY V1000 User Manual No. Parameter Name Description Mu H4-01 (Te Sel lti-Function Analog 1 rminal AM Monitor ection) Select the data to output through multi-function analog output terminal AM. Set the desired monitor parameter to the digits available in U†-††. For example, enter “103” for U1-03.

When using this terminal as a through terminal or when not using it at all, set “000” or “031”. H4-02 Mu (Te lti-Function Analog 1 rminal AM Output Gai Sets the output voltage level terminal AM at 100 % of the selected output value. The gain is adjustable from -999.9% to 999.9% where 100.0 % is n) equal to 10 V output. H4-03 Mu (Te lti-Function Analog 1 rminal AM Bias Setting Sets the output voltage level terminal AM at 0 % of the selected output value. The bias is adjustable from -999.9% to 999.9% where 100.0 % is ) equal to 10 V output. Step D isplay/Result 1. Turn on the power to the drive. The initial display appears. ⇒ 2. Press until the Parameter setting menu is displayed. ⇒ 3.

Press to enter the Parameter setting menu. ⇒ 4. Press and to select H4-01. ⇒ 5. Press to display the value currently set to H4-01. ⇒ 6. Press and to set the output current (103). ⇒ 7. Save the setting by pressing . ⇒ 8. The display automatically returns to the parameter setting menu. ⇒