omron — Analog Outputs: H4-01 to H4-03

4.6 Basic Drive Setup Adjustments ◆ Digital Outputs H2-01 to H2-03 Parameters H2-01, H2-02 and H2-03 assign functions to digital output terminals MA, MB, MC, P1, and P2. Set these parameters as required by the application. Default values are listed below. NOTICE: Do not assign a function that repeats ON/OFF frequently to terminals MA and MB. Failure to comply will reduce the relay contact lifetime. The expected number of relay contact switching times is normally 200,000 times (current 1 A, resistance load). Start-Up Programming & Operation Note: The setting range for H2-01 through H2-03 is 0 to 14D. Refer to Parameter List on page 293 for more information.

Figure 4.25 Multi-Function Contact Outputs 250 Vac, 10 mA - 1 A 30 Vdc, 10 mA - 1 A (standard default setting) 4 MA MB Fault MC Fault Multi-Function Open-Collector Outputs 48 Vdc, 2 to 50 mA (standard default setting) P1 During Run (Open-Collector 1) Speed Agree Open-Collector Common (Open-Collector 1) Figure 4.25 Digital Output Connection Diagram ◆ Analog Outputs: H4-01 to H4-03 Group U parameters can be used to observe the drive status (operating conditions) through the LED operator. Analog outputs corresponding to these monitors can be obtained on analog output terminal AM or Fm when programmed with parameter group H4. Some Group U monitors are not available as analog outputs.

OYMC TOEP C71060622-01-OY V1000 User Manual 139 No. Parameter Name Default H2-01 Terminal MA, MB and MC Function Selection (relay) E: Fault H2-02 Terminal P1 Function Selection (open-collector) 0: During Run H2-03 Terminal P2 Function Selection (open-collector) 2: Speed Agree 1 PC