4.6 Basic Drive Setup Adjustments Parameters E2-07 through E2-08 and E2-12 may be difficult to set manually. If Auto-Tuning is not possible, simply leave these settings at the default values. 138 OYMC TOEP C71060622-01-OY V1000 User Manual No. Parameter Name Setting Method E2-01 Motor Rated Current Sets the motor nameplate full load current in amperes (A). E2-02 Motor Rated Slip Calculate and set the motor rated slip based on the rated speed described on the motor nameplate. Motor rated slip = Motor rated frequency [Hz] - Rated speed [r/min] x No. of motor poles / 120. E2-03 Motor No-Load Current Set motor no-load current at rated voltage and rated frequency.
Contact the motor manufacturer to get the no-load current. This information is not usually written on the motor nameplate. The default no-load current is for a Yaskawa 4-pole motor. E2-04 Number of Motor Poles Displayed only when OLV control mode is selected. Set the number of motor poles described on the motor nameplate. E2-05 Motor Line-to-Line Resistance This value is automatically set during Auto-tuning. When regular Auto- Tuning is not possible, contact the motor manufacturer to find out the line-to- line resistance. If using the Motor Test Report, calculate resistance between lines as follows: E-Type Insulation:
Test Report value for line resistance at 75 °C at 0.92 ohms B-Type Insulation: Test Report value for line resistance at 75 °C at 0.92 ohms F-Type Insulation: Test Report value for line resistance at 115 °C at 0.87 ohms E2-06 Motor Leakage Inductance Set the amount of voltage drop due to motor leakage inductance at base frequency and motor rated current.This value should be set when using a high- speed motor or another type of motor that has a relatively small amount of inductance. Contact the motor manufacturer to get the motor leakage inductance, as this information is not usually written on the motor nameplate.
E2-07 Motor Iron-Core Saturation Coefficient 1 This value is automatically set during rotational Auto-Tuning. E2-08 Motor Iron-Core Saturation Coefficient 2 This value is automatically set during rotational Auto-Tuning. E2-09 Motor Mechanical Loss Displayed only when using Open Loop Vector Control. It is not necessary to set this parameter, but it may require adjustment under the following circumstances: Large amount of torque loss relative to motor bearings Fan and pump type applications with a large amount of torque loss The amount of mechanical loss will be reflected in the amount of torque compensation. E2-10 Motor Iron Loss for Torque Compensation Displayed only when using V/f Control.
Increase the motor iron loss in watts in order to increase the accuracy of torque compensation. E2-11 Motor Rated Output Sets the motor rated power in kilowatts (kW). This value is automatically set during Auto-Tuning in units of 0.01. E2-12 Motor Iron-Core Saturation Coefficient 3 Set to the motor iron saturation coefficient at 130% of magnetic flux. This value is automatically set during rotational Auto-Tuning.