omron — Motor Protection: L1-01 and L1-02

4.6 Basic Drive Setup Adjustments Start-Up Programming & Operation A: Typical maximum speed for Yaskawa motor frame number 200LJ and greater B: Typical maximum speed for Yaskawa motor frame numbers 160MJ – 180LJ C: Typical maximum speed for Yaskawa motor frame number 132MHJ or less D: Typical maximum speed for Yaskawa motor frame number 132MJ or less 4 Notes on Motor Protection • Motor protection meeting UL and cUL standards is achieved with the motor overload protection time (L1-02) set to factory default setting. Normally, L1-02 (Motor Overload Protection Time) does not require setting.

If the motor overload tolerance is clear, set the overload protection time at hot start according to the motor. To detect overload earlier, Note: Figure 4.27 Figure 4.27 Motor Protection Operation • Disable motor protection (L1-01 = 0) when running multiple motors from the same drive. Attach a thermal relay for each motor to provide overload protection. • Use L1-13 (Continuous Electrothermal Operation Selection) to select whether the electrothermal value is “held” or “not held” when power supply is turned off. Default setting is 1 (Enabled).

OYMC TOEP C71060622-01-OY V1000 User Manual 145 L1-01 Setting Motor Type Overload Tolerance Cooling Fan Capacity Electrothermal Protection (100% motor overload) 4 PM Derated Torque Motor Pico motors feature a heatsink running from the flange to the enclosure. IPM motors for derated torque have the most effective cooling design. Because this motor is designed for derated torque applications, limit the load at low speeds. 150 (%)120 60 s momentary 100 rating Torque 80 continuous rating 50 0.0 10 33 100 Motor Speed (%) QWVRWV HTGSWGPE[ 60 s momentary rating continuous rating s 4 etting. .27 illustrates motor protection operation time characteristics.

Operation Time (minutes) 10 7 3 Cold Start 1 0.4 Hot Start 0.1 Motor Current (%) 0 100 150 200 E2-01 = 100% 7 3 1 0.4 0.1 0 100 150 200