4.7 Test Run 4.7 Test Run ◆ Powering Up the Drive and Operation Status Display ■ Powering Up the Drive Review the following checklist before turning the power on. Start-Up Programming & Operation 4 ■ Status Display When the power supply to the drive is turned on, the LED operator lights will appear as follows: Auto-Tuning automatically sets and tunes parameters required for motor operation. OYMC TOEP C71060622-01-OY V1000 User Manual 149 Item to Check Description En 20 20 Power supply voltage 40 Pro (fo Ch sure the power supply voltage is correct: 0 V class: single-phase 200 to 240 Vac 50/60 Hz 0 V class: 3-phase 200 to 240 Vac 50/60 Hz 0 V class:
3-phase 380 to 480 Vac 50/60 Hz perly wire the power supply input terminals (R/L1, S/L2, T/L3). r single-phase 200 V class models, wire only R/L1 and S/L2) eck for proper grounding of drive and motor. Drive output terminals Pro and motor terminals an perly wire drive output terminals U/T1, V/T2, and W/T3 with motor terminals U, V, d W. Control circuit terminals Ch eck control circuit terminal connections. Drive control terminal Op status en all control circuit terminals (off). Status of the load and Un connected machinery couple the motor from the load. No. Name Description Normal Operation The data display area displays the frequency reference. flashes.
Fault Ma oltage (ex) Data displayed varies by the type of fault. Refer to Fault Displays, Causes, and Possible Solutions on page 183 for more information and corrective action. and are lit. in circuit low v ◆ Auto- Tuning