4.7 Test Run • The motor should accelerate and decelerate smoothly. ■ Operation Instructions The following example illustrates a procedure to run the drive using the digital operator. Note: Before starting the motor, set the frequency reference to 6 Hz. Refer to The Drive and Programming Mode on page 93 for instructions. 158 OYMC TOEP C71060622-01-OY V1000 User Manual Step Display/Result 1. Turn on the power to the drive. The initial display appears. ⇒ Press the key to select LOCAL. The LO/RE LED will 2. turn on. ⇒ STOP Flashing Off 3. Press RUN to give the drive a run command. RUN will light and the motor will rotate at 6 Hz.
⇒ STOP Off On Ensure the motor is rotating in the correct direction and no faults or 4. alarms occur. ⇒ Motor Forward If there is no error in step 4, press to increase the frequency reference. Increase the frequency in 10 Hz increments verifying smooth operation results at all speeds. For each frequency monitor 5. the drive output current (U1-03) through the LED operator to confirm the current is well below the motor rated current. Example: 6 Hz → 50 Hz/60 Hz. Note: Refer to Auto-Tuning Errors on page 182 for help with errors that occur while Auto-Tuning the drive.