4.7 Test Run ◆ Jog Operation: FJOG/RJOG Digital inputs programmed as Forward Jog (H1- …… = 12) and Reverse Jog (H1- …… = 13) will be Jog inputs that do not require a run command. Closing the terminal set for Forward Jog input will cause the drive to ramp to the Jog Frequency Reference (d1-17) in the forward direction. The Reverse Jog will cause the same action in the reverse direction. The Forward Jog and Reverse Jog can be set independently. ■ Jog Operation Parameters ■ Selections for Digital Input Terminals S1 to S6 (H1-01 to H1-06) ■ Connection Example for the Jog Function In this example, H1-06 = 12 and d1-17 = 6.0 Hz.
Figure 4.30 Figure 4.30 Jog Command from External Terminals 162 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Setting Range Default Setting d1-17 Jog Frequency Reference Frequency reference when: “Jog Frequency Reference” is selected via multi-function input terminals. “Jog Frequency Reference” has priority over “Multi-Step Speed Reference 1 to 16." Parameter d1-17 also sets the frequecny reference for the the multi-function input commands“Forward Jog” and “Reverse Jog.” 0.00 to 400.00 6.00 Hz Setting Name 12 FJOG Command (ON: rotates forward at the Jog frequency set to d1-17) 13 RJOG Command (ON:
rotates in reverse at the Jog frequency set to d1-17) Three-Phase 200 Vac (400 Vac) Drive R/L1 U/T1 S/L2 V/T2 T/L3 W/T3 S6 (FJ0G) SC M