omron — 4.8 Test Run Checklist

4.8 Test Run Checklist Proceed to the following checklist after checking items 4 through 9. 168 OYMC TOEP C71060622-01-OY V1000 User Manual No. Checklist Page 10 The should illuminate after giving a run command. 11 To give a run command and frequency reference from the LED Digital Operator, press to set to LOCAL. The LO/RE key lights while LOCAL is displayed. 99 12 If the motor rotates in the opposite direction during the test run, switch two of the drive output terminals (U/T1, V/T2, W/T3). 149 13 Select the correct duty rating (C6-01) for the application.

130 14 Set the correct values for the motor rated current (E2-01) and the motor protection selection (L1-01) to ensure motor thermal protection. 141 15 If the run command and frequency reference are provided via the control circuit terminals, set the drive for REMOTE and be sure the LO/RE light is out. 99 16 If the control circuit terminals should supply the frequency reference, select the correct voltage input signal level (0 to 10 V) or the correct current input signal level (4 to 20 mA or 0 to 20 mA). 99 17 Set the proper voltage to terminal A1. (0 to 10 V) 120 18 Set the proper current to terminal A2.

(4 to 20 mA or 0 to 20 mA) 121 19 When current input is used, set H3-09 to “2” (4 to 20 mA) or “3” (0 to 20 mA) and set H3-10 to “0”. 121 20 When current input is used, switch the drive built-in DIP switch S1 from V-side (OFF) to I-side (ON). 121 21 Set the minimum and maximum frequency references to the desired values. Make the following adjustments if the drive does not operate as expected: Gain adjustment: Set the maximum voltage/current signal and adjust the analog input gain (H3-03 for input A1, H3-11 for input A2) until the frequency reference value reaches the desired value. Bias adjustment:

Set the minimum voltage/current signal and adjust the analog input bias (H3-04 for input A1, H3-12 for input A2) until the frequency reference value reaches the desired minimum value.