5.2 Motor Performance Fine Tuning 5.2 Motor Performance Fine Tuning This section offers helpful information for counteracting oscillation, hunting, or other faults that occur while performing a trial run. Refer to the section below that corresponds to the motor control method used. Note: This section describes parameters that are commonly edited. Consult OYMC or an OYMC sales representative for more information on detailed settings and fine-tuning the drive. ◆ V/f Motor Control Method Tuning Table 5.1 Parameters for Tuning the Drive in V/f Motor Control Method Troubleshooting 5 OYMC TOEP C71060622-01-OY V1000 User Manual 173 Problem Parameter No.
Countermeasure Default Value Suggested Setting • Motor hunting and oscillation at speeds between 10 and 40 Hz Hunting Prevention Gain (n1-02) • If insufficient motor torque relative to the size of the load causes hunting, reduce the setting. • When motor hunting and oscillation occur with a light load, increase the setting. 1.00 0.50 to 2.00 • Motor noise • Motor hunting and oscillation at speeds up to 40 Hz Carrier Frequency Selection (C6-02) • If the motor noise is too loud, increase the carrier frequency. • When motor hunting and oscillation occur at speeds up to 40 Hz, lower the carrier frequency.
• The default setting for the carrier frequency depends on the drive capacity (o2-04) and the Drive Duty Selection (C6-01). dep. on drive capacity 1 to A • Poor torque or speed response • Motor hunting and oscillation Torque Compensation Primary Delay Time (C4-02) • If motor torque and speed response are too slow, decrease the setting. • If motor hunting and oscillation occur, increase the setting. 200 ms 100 to 1000 ms • Poor motor torque at speeds below 10 Hz • Motor hunting and oscillation Torque Compensation Gain (C4-01) • If motor torque is insufficient at speeds below 10 Hz, increase the setting. • If motor hunting and oscillation with a relatively light load, decrease the setting.
1.00 0.50 to 1.50 • Poor motor torque at low speeds • Motor instability at motor start Mid Output Voltage A (E1-08) Minimum Output Voltage (E1-10) • If torque is insufficient at speeds below 10 Hz, increase the setting. • If motor instability occurs at motor start, decrease the setting. Note: The recommended setting value is for 200 V class drives. Double this value when using a 400 V class drive. E1-08: 16.0 V E1-10: 12.0 V Initial value ±5 V • Poor speed precision Slip Compensation Gain (C3-01) • After setting the motor-rated current (E2-01), motor-rated slip (E2-02) and motor no-load current (E2-03), adjust the slip compensation gain (C3-01). - 0.5 to 1.5