5.2 Motor Performance Fine Tuning Default settings change when the Control Method is changed (A1-02) or a different V/f pattern is selected using parameter E1-03. The default setting shown is for V/f Control. Note: Use slip compensation to improve speed precision in V/f Control. First make sure that the proper values have been set for the motor rated current to E2-01, motor rated slip (E2-02), and motor no-load current (E2-03). Next, adjust the slip compensation gain set to C3-01 so that it is between 0.5 to 1.5.
◆ Open Loop Vector (OLV) Motor Control Method Tuning Table 5.2 Parameters for Tuning the Drive in OLV Motor Control Method 174 OYMC TOEP C71060622-01-OY V1000 User Manual Problem Parameter No. Countermeasure Default Value Suggeste d Setting • Poor motor torque and speed response • Control motor hunting and oscillation at speeds between 10 and 40 Hz. AFR Gain (n2-01) • If motor torque and speed response are too slow, gradually decrease the setting by 0.05. • If motor hunting and oscillation occur, gradually increase the setting by 0.05. 1.00 0.50 to 2.00 • Poor motor torque and speed response • Control motor hunting and oscillation at speeds between 10 and 40 Hz.
AFR Time Constant 1 (n2-02) • To improve motor torque speed response, gradually reduce this setting by 10 ms and check the performance. • If motor hunting and oscillation occur as a result of load inertia, gradually increase the setting by 50 ms and check the performance. Note: Ensure that n2-02 ≤ n2-03. When making adjustments to n2- 02, set C4-02 (Torque Compensation Primary Delay Time Constant 1) accordingly. 50 ms 50 to 2000 ms • Overvoltage trips when accelerating, decelerating, or during sudden speed or load changes. AFR Time Constant 2 (n2-03) • If overvoltage trips occur, gradually increase this setting by 50 ms. • If response is slow, gradually reduce this setting by 10 ms. Note:
Ensure that n2-02 ≤ n2-03. When making adjustments to n2- 03, increase the value of C4-06 (Torque Compensation Primary Delay Time 2) proportionally. 750 ms 750 to 2000 ms Torque Compensation Primary Delay Time Constant 2 (C4-06) • If overvoltage trips occur, gradually increase this setting by 10 ms and check the performance. • If response is slow, gradually reduce this setting by 2 ms and check the performance. Note: Ensure that C4-02 ≤ C4-06. When changing C4-06 (Torque Compensation Primary Delay Time Constant 2), increase the value of n2-03 proportionally. 150 ms 150 to 750 ms