omron — Motor Hunting and Oscillation Control Parameters

5.2 Motor Performance Fine Tuning Troubleshooting 5 Default settings change when the Control Method is changed (A1-02) or a different V/f pattern is selected using parameter E1-03. The default setting shown is for V/f Control. When using OLV Motor Control, leave the torque compensation gain (C4-01) at its default setting of 1.00. To increase speed precision during regeneration in OLV Motor Control, enable slip compensation during regeneration (C3-04 = “1”). ◆ Motor Hunting and Oscillation Control Parameters In addition to the parameters discussed in V/f Pattern Selection: E1-03 on page 134 , the following parameters indirectly affect motor hunting and oscillation.

OYMC TOEP C71060622-01-OY V1000 User Manual 175 Problem Parameter No. Countermeasure Default Value Suggeste d Setting • Poor motor torque and speed response • Motor hunting and oscillation. Torque Compensation Primary Delay Time Constant 1 (C4-02) • To improve motor torque speed response, gradually reduce this setting by 2 ms and check the performance. • If motor hunting and oscillation occur, gradually increase this setting by 10 ms. Note: Ensure that C4-02 ≤ C4-06. When making adjustments to C4-02, increase n2- 02 (AFR Time Constant) proportionally.

20 ms 20 to 100 ms • Poor speed response and stability Slip Compensation Primary Delay Time Constant (C3-02) • If response is slow, gradually decrease the setting by 10 ms. • If speed is unstable, gradually increase the setting by 10 ms. 200 ms 100 to 500 ms • Poor speed precision Slip Compensation Gain (C3-01) • If speed is too slow, gradually increase the setting by 0.1 ms. • If speed is too fast, gradually decrease the setting by 0.1 ms. 1.0 0.5 to 1.5 • Motor noise • Control motor hunting and oscillation occur at speeds below 10 Hz. Carrier Frequency Selection (C6-02) • If there is too much motor noise, the carrier frequency is too high.

• If motor hunting and oscillation occur at low speeds, reduce the carrier frequency. • The default setting for the carrier frequency depends on the drive capacity (o2-04) and Drive Duty Selection (C6-01). dep. on drive capacity 0 to the default setting • Poor motor torque at low speeds • Poor speed response • Motor instability at motor start. Mid Output Voltage A (E1-08) Minimum Output Voltage (E1-10) • If motor torque and speed response are too slow, increase the setting. • If the motor exhibits excessive instability at start-up, reduce the setting. Note: The default value is for 200 V class units. Double this value when using a 400 V class drive.

When working with a relatively light load, increasing this value too much can create an excessively high of a torque reference. E1-08: 12.0 V E1-10: 2.5 V Initial ±2 V