5.2 Motor Performance Fine Tuning Table 5.3 Parameters that Affect Control Performance in Applications 176 OYMC TOEP C71060622-01-OY V1000 User Manual Name (Parameter No.) Application Dwell Function (b6-01 through b6-04) Prevents motor speed loss by maintaining the output frequency when working with heavy loads or when there is powerful backlash on the machine side. Accel/Decel Time (C1-01 through C1-11) Adjusting accel and decel times will affect the torque presented to the motor during acceleration or deceleration. S-Curve Characteristics (C2-01 through C2-04) Prevents shock at the beginning and end of acceleration and deceleration.
Jump Frequency (d3-01 through d3-04) Skips over the resonant frequencies of connected machinery. Analog Filter Time Constant (H3-13) Prevents fluctuation in the analog input signal due to noise. Stall Prevention (L3-01 through L3-06, L3-11) • Prevents motor speed loss and overvoltage. Used when the load is too heavy and also during sudden acceleration/deceleration. • Adjustment is not normally required because Stall Prevention is enabled as a default. Disable Stall Prevention during deceleration (L3-04 = “0”) when using a braking resistor. Torque Limits (L7-01 through L7-04, L7-06, L7-07) • Sets the maximum torque for Open Loop Vector Control.
• Ensure that the drive capacity is greater than the motor capacity when increasing this setting. Be careful when reducing this value because motor speed loss may occur with heavy loads.