omron — Fault Displays, Causes, and Possible Solutions

5.4 Fault Detection 5.4 Fault Detection ◆ Fault Displays, Causes, and Possible Solutions Table 5.8 Detailed Fault Displays, Causes, and Possible Solutions Troubleshooting 5 OYMC TOEP C71060622-01-OY V1000 User Manual 183 LED Operator Display Fault Name bUS Option Communication Error • After establishing initial communication, the connection was lost. • Only detected when the run command frequency reference is assigned to an option card. Cause Possible Solution No signal received from the PLC. • Check for faulty wiring. • Correct the wiring. • Check for loose wiring and short circuits. Repair as needed. The communication cable is faulty or a short circuit exists.

A communications data error occurred due to noise. • Check the various options available to minimize the effects of noise. • Counteract noise in control circuit, main circuit, and ground wiring. • Ensure that other equipment such as switches or relays do not cause noise and use surge suppressors if required. • Use cables recommended by OYMC or another type of shielded line. Ground the shield on the controller side or on the drive input power side. • Separate all wiring for communications devices from drive input power lines. Install a noise filter to the input side of the drive input power. The option card is damaged.

• Replace the option card if there are no problems with the wiring and the error continues to occur. The option card is not properly connected to the drive. • The connector pins on the option card are not properly lined up with the connector pins on the drive. • Reinstall the option card. LED Operator Display Fault Name CE MEMOBUS/Modbus Communication Error Control data was not received for the CE detection time set to H5-09. Cause Possible Solution Faulty communications wiring, or a short circuit exists. • Check for faulty wiring. • Correct the wiring. • Check for loose wiring and short circuits. Repair as needed. A communications data error occurred due to noise.

• Check the various options available to minimize the effects of noise. • Counteract noise in control circuit, main circuit, and ground wiring. • Ensure that other equipment such as switches or relays do not cause noise and use surge suppressors if required. • Use OYMC-recommended cables, or another type of shielded line. Ground the shield on the controller side or on the drive input power side. • Separate all wiring for communications devices from drive input power lines. Install a noise filter to the input side of the drive input power.