5.4 Fault Detection 184 OYMC TOEP C71060622-01-OY V1000 User Manual LED Operator Display Fault Name CF Control Fault A torque limit was reached continuously for three seconds or longer during a ramp to stop while in Open Loop Vector Control. Cause Possible Solution Motor parameters are not set properly. Check the motor parameter settings and repeat Auto-Tuning. Torque limit is too low. Set the torque limit to the most appropriate setting (L7-01 through L7-04). Load inertia is too big. • Adjust the deceleration time (C1-02, -04, -06, -08). • Set the frequency to the minimum value and interrupt the run command when the drive finishes decelerating.
LED Operator Display Fault Name CoF Current Offset Fault There is a problem with the current detection circuit or the drive attempted to start a coasting PM motor. Cause Possible Solution While the drive automatically adjusted the current offset, the calculated value exceeded the allowable setting range. This problem may occur when attempting to restart a coasting PM motor. Enable Speed Search at start (b3-01 = 1). Use the multi-function terminals to execute External Speed Search 1 and 2 (H1- . = 61 or 62). NOTE: When using a PM motor, both External Speed Search 1 and 2 perform the same operation. LED Operator Display Fault Name CPF02 A/D Conversion Error An A/D conversion error occurred.
Cause Possible Solution Control circuit is damaged. Cycle power to the drive. If the problem continues, replace the drive. Control circuit terminals have shorted out (+V, AC). • Check for wiring errors along the control circuit terminals. • Correct the wiring. Check the resistance of the speed potentiometer and related wiring. Control terminal input current has exceeded allowable levels. • Check the input current. • Reduce the current input to control circuit terminal (+V) to 20 mA. LED Operator Display Fault Name CPF03 PWM Data Error There is a problem with the PWM data. Cause Possible Solution Drive hardware is damaged. Replace the drive.
LED Operator Display Fault Name CPF06 EEPROM Data Error There is an error in the data saved to EEPROM.